SPC25/3+1

PARAMETERS

Test class according to EN 61643-11 ed. 2 and IEC 61643-11   TYP1+2, CLASS I+II
Network type   TN-S
TT
Maximum continuous operating voltage UC 275 V AC / 350 V DC
Impulse discharge current for class I test (10/350) L/N limp 25 kA
Charge L/N Q 12,5 As
Specific energy for class I test L/N W/R 156 kJ/Ω
Impulse discharge current for class I test (10/350) N/PE Iimp 100 kA
Charge N/PE Q 50 As
Specific energy for class I test N/PE W/R 2500 kJ/Ω
Total discharge current (10/350) L1+L2+L3+N->PE Itotal 100 kA
150 kA
Nominal discharge current for class II test (8/20) In 25 kA
Maximum discharge current Imax 50 kA
Voltage protection level Up < 1,2 kV
Temporary overvoltage (TOV) L/N UT 335 V/5 s
Temporary overvoltage (TOV) N/PE UT 1200 V/0,2 s
Response time L/N tA < 25 ns
Response time N/PE tA < 100 ns